Standards Selection – select between UL, ULC, and Manual Mode If using dialer capture, configure the BAT-Fire conditions that will cause phone line 2 voltage to be dropped, alerting the FACP For inputs, select the CID signal that will be relayed when the input is triggered, specify the Zone Number, and name the input For outputs, name the output and select the conditions for which the output will be triggered Configuration mode will timeout after 1 hour if the cover tamper is open and 90 seconds if the cover tamper is closed b. Note: Evaluation PCBs may be labelled “WPS” instead of “CONFIG” This enables editing of the configuration fields within Alula Connect.

On site – Press the CONFIG button on the BAT-Fire. See BAT-Fire Manual, pages 2-4 Programming the BAT-FireĪ. Follow the manual for your FACP installation modeī.
#ALULA BAT CONNECT INSTALL#

The phone line inputs of the BAT-Fire are not used. Point Capture – FACP inputs and outputs are connected to BAT-Fire outputs and inputs.Programmable I/O ports may be used to monitor additional I/O of interest. Phone Line Capture – Connecting the Tip/Ring lines of the FACP into the BAT-Fire phone line inputs and capturing the FACP dial out signalling.